Table of Contents

Identifying Rope CTs

Overview

The eGauge supports Rope CTs from three different manufacturers. In order to determine which CT to select, refer to the tables below.

eGauge branded CTid rope CTs (ERA-106-xxxx) are not meant to be manually set and should be scanned using the CTid function accessed from the eGauge Installation Settings page.  For more information please see: Configuring CTid enabled sensors.

JD CTs

For JD CTs (colored red) there will be a label located on the CT clip itself:

CT Labeling

CT Identifier on eGauge Install Page

JRFS 115

JD JRFS 115mm/4.53" 4085A

JRFS 190

JD JRFS 190mm/7.48" 4085A

 

 
 

AE Accuenergy CTs

For AE Accuenergy CTs (colored orange), there is a label located on the CT lead:

CT Labeling

CT Identifier on eGauge Install Page

RCT16-1000

AE RCT 106mm/4.17" 2775A

RCT24-1000

AE RCT 178mm/7.01" 2775A

RCT24-2500

AE RCT 178mm/7.01" 6935A

RCT36-2500

AE RCT 271mm/10.67" 6935A

 

 
 

Magnelab CTs

For the Magnelab CTs (colored green) there is a label located on the outside of the CT clip:

CT Labeling

CT Identifier on eGauge Install Page

RCT-1800-COIL

ML RCT 152.4mm/6.00" 4800A

RCT-2400-COIL

ML RCT 203.2mm/8.00" 4800A

RCT-3600-COIL

ML RCT 279.4mm/11.00" 4800A

 

 
 

 

Note that eGauge no longer stocks Magnelab Rope CTs, but you may encounter them in the field (and the eGauge still supports them). They read very poorly below about 50A. If the CT features a separate calibration tag, this should be noted.

Additional CT types are supported - see our CT Selection Guide for a more comprehensive overview. Connecting CTs which do not meet requirements for supported CTs may result in reduced accuracy or damage to the eGauge.