Overview
The eGauge Core WiFi (EG4215) is the base WiFi version of the EG4xxx meter line. It has 15 sensor inputs and integrated Ethernet and WiFi communication. See the Meter Comparison Chart for the different versions of the EG4xxx meter line and what is the best fit.
The eGauge Core WiFi combines an energy meter, data logger, and a web server. This powerful combination lets you measure, store and retrieve data directly from the device or from a remote location. Not only does it calculate power (V, A, VAr, kWh, etc), but also data from optional sensors that assess flow rate, temperature, wind speed, and more. You can view historical and live data for up to 30 years with the unit’s convenient user interface (UI). The UI can be accessed on a local network or via the internet from a computer, tablet, or smartphone. Once connected, you have access to real-time values, long-term reports, an interactive graphical interface, and many other tools. The best part is that you pay nothing for the user interface because you retrieve data directly from your own eGauge hardware, not a cloud or 3rd party host.
Measurements & Operation
- AC Voltage: ≤ 277V L-N, ≤ 480V L-L
- DC Voltage: +/- 60Vdc (9Vdc minimum to power)
- Frequency: 50/60Hz
- Power Draw: 12W max, 2W typical
- Accuracy: ANSI C12.2 - 0.5% Compliant
- 15 Sensor ports
Data Logger Capacity
- Most recent hour: 1-second granularity
- Most recent year: 1-minute granularity
- Most recent 10-years: 15-minute granularity
- Lifetime: 1-day granularity
Communication
- Ethernet: IEEE 802.3 - LAN
- WiFi: IEEE 802.11n/b/g 2.4 GHz
- Cell optional with third party hardware
Safety and Regulatory
- Safety: IEC/UL 61010-1 Ed. 3.0 B:2010
- CE
- IEC 61000-6-1 Ed. 3.0 B:2016
- IEC 61000-6-3 Ed. 2.1 B:2011
- FCC
- FCC Title 47 CFR Part 15-Subpart B Class B
- ICES-003 Information Technology Equipment Class B
Environmental
- Operating Temperature: -30 to 70 deg C (-22 to 158 F)
- Max Altitude 4000m (13,123ft)
- Max Humidity: 80% up to 31 deg C
- Measurement Category: Overvoltage Category III
- Location: Open type indoor device
- Pollution Degree: 2
- 1x eGauge EG4215 Main Unit
- 1x 5-pin AC power plug
- 1x 2-pin DC power plug
- 1x WiFi antenna
- 1x Quick Start Guide
Optional Common Hardware Accessories (not included)
- Current Transformers (CTs) w/8 ft wires & plug (as ordered)
- Other CTid-enabled Sensors