eGauge Core (EG4015)

Visit the online store page

Model: EG4015

EG4015
EG4015

 

Overview

The eGauge Core (EG4015) is the base version of the EG4xxx meter line. It has 15 sensor inputs and integrated Ethernet communication. See the Meter Comparison Chart for the different versions of the EG4xxx meter line and what is the best fit.


The eGauge Core combines an energy meter, data logger, and a web server. This powerful combination lets you measure, store and retrieve data directly from the device or from a remote location. Not only does it calculate power (V, A, VAr, kWh, etc), but also data from optional sensors that assess flow rate, temperature, wind speed, and more. You can view historical and live data for up to 30 years with the unit’s convenient user interface (UI). The UI can be accessed on a local network or via the Internet from a computer, tablet, or smartphone. Once connected, you have access to real-time values, long-term reports, an interactive graphical interface, and many other tools. The best part is that you pay nothing for the user interface because you retrieve data directly from your own eGauge hardware, not a cloud or 3rd party host.

Specifications

Measurements & Operation

  • AC Voltage: ≤ 277V L-N, ≤ 480V L-L
  • DC Voltage: +/- 60Vdc (9Vdc minimum to power)
  • Frequency: 50/60Hz
  • Power Draw: 12W max, 2W typical
  • Accuracy: ANSI C12.2 - 0.5% Compliant
  • 15 Sensor ports

Data Logger Capacity

  • Most recent hour: 1-second granularity
  • Most recent year: 1-minute granularity
  • Most recent 10-years: 15-minute granularity
  • Lifetime: 1-day granularity

Communication

  • Ethernet: IEEE 802.3 - LAN
  • WiFi/Cell optional with third party hardware

Safety and Regulatory

  • Safety: IEC/UL 61010-1 Ed. 3.0 B:2010
  • CE
    • IEC 61000-6-1 Ed. 3.0 B:2016
    • IEC 61000-6-3 Ed. 2.1 B:2011
  • FCC
    • FCC Title 47 CFR Part 15-Subpart B Class B
    • ICES-003 Information Technology Equipment Class B

Environmental

  • Operating Temperature: -30 to 70 deg C (-22 to 158 F)
  • Max Altitude 4000m (13,123ft)
  • Max Humidity: 80% up to 31 deg C
  • Measurement Category: Overvoltage Category III
  • Location: Open type indoor device
  • Pollution Degree: 2
 
 

Included Hardware

  • 1x eGauge Core EG4015 Main Unit
  • 1x 5-pin AC power plug
  • 1x 2-pin DC power plug
  • 1x Quick Start Guide

Optional Common Hardware Accessories (not included)