Table of Contents

Low Voltage / Dry Contact Sensor (ELV2)

Use this template to create a main support article for a hardware product

Visit the online store page

Model: ELV2

ELV2 and included RJ-11 cable

CTid

Requires the eGauge Sensor Hub and EG4xxx model or newer eGauge. This hardware is not compatible with older model eGauge meters. Analog sensors require ≤ 50 Ω output

 

 

The eGauge 2V Analog Input is used in conjunction with the Sensor Hub and an EG4xxx model meter (Core or Pro) which allows EG4xxx meters to read 0 -- 2V low-impedance analog values or states from standard 2-wire dry contacts such as relays.

 

 

Specifications

  • CTid Enabled (w/ auto-configure and locator LED)
  • Compatible with
    • 2-wire dry contact or relay
    • 0 to 2 volt analog output sensors with ≤ 50Ω impedance
  • 4.7 kΩ pull-up resistor between Signal and 2V
  • Signal pin: open- 2V; closed- 0V
  • -30 °C to 70 °C
  • Humidity range: Up to 80%
  • Extruded aluminum Case
  • 26 x 26 x 40 (mm), 1.02 x 1.02 x 1.57 (in.)
  • 7' RJ-11 cable for Sensor to Sensor Hub
  • 47 CFR Part 15, Subpart B – Unintentional Radiators, Class B for Home or
    Commercial use
  • US Patent # 10560763
  • 2-year limited warranty
 
 

Included Hardware

  • (1) eGauge Low Voltage Sensor
  • (1) 3-pin input plug
  • (1) 7’ RJ-11 cable for connection to Sensor Hub