Overview
Voltage registers are configured in much the same way as power registers (the default register type on the eGauge). Follow the steps in this article to add a register to record Voltage input.
Prerequisites
To make settings changes you will need access to the eGauge interface and valid login credentials.
- These steps assume a minimum firmware version of 4.0. Instructions for earlier versions are at the end of this article.
Instructions
Step 1: Access the Installation Settings page by navigating to Setup → Other settings. Then click Installation to the right.
Step 2: Under Registers, click the "Add Register" button
Step 3: Name the register as appropriate.
Step 4: Using the dropdown menu, change the register type from "P" to "L"

Step 5: In the next dropdown menu, select the appropriate voltage reference.

- L1, L2, L3 use the high-voltage AC line inputs relative to N terminal
- L1-L2, L2-L3, L3-L1 use the high-voltage AC line inputs as line-to-line voltages
- D1, D2, D3 use the high-voltage AC line inputs with a virtually calculated neutral (not commonly used and still requires N connection)
- Ldc uses the 2-pin DC voltage input
Step 6: In the final dropdown menu select the measurement type.

- normal value records RMS voltage (e.g., for AC voltages)
- DC-only (mean) value records the mean value (e.g., for Ldc input)
- frequency records the frequency of the input. Frequencies are counted as zero-level crosses, so DC voltages will typically display 0 Hz.
Step 7: Repeat these steps to add additional registers, if needed. Click Save at the bottom of the page to save your changes.
Legacy (pre firmware 4.0)
- Navigate to Settings → Installation
- Under Registers, click the "Add Registers" button
- Name the register as appropriate
- Using the dropdown menu, change the register type from "P" to “V”
- A second dropdown menu will appear. Select the appropriate voltage reference
- Click "Save" at the bottom of the page when finished (valid credentials required)