Overview
The eGauge can be set to record individual CT amperages as separate registers. Unlike power registers, amperage registers are absolute values (they do not change polarity to reflect the directional flow of current).
Instructions
Firmware 4.0 & Later
Step 1: Click the menu(≡) in the upper left, then select Setup → Other Settings

Step 2: Click on Installation on the left side

Step 3: Under Registers click the Add Register button, then name the Register

Step 4: In the Recorded value/formula: use the dropdown to change the register type from P to S, in the next dropdown select the correct sensor number

Step 5: In the final dropdown menu, select the measurement type (If in doubt, ‘Normal Value’ is generally correct)
Step 6: Scroll to the bottom of the page and click Save. As with all physical registers, data will ONLY start recording from the time the register is created.
Legacy (Pre-Firmware 4.0)
Navigate to Settings -> Installation
Under Registers, click the "Add Registers" button
Name the register as appropriate
Using the dropdown menu, change the register type from "P" to "I"
A second dropdown menu will appear. Select the appropriate CT number
Click "Save" at the bottom of the page when finished (valid credentials required)