Certification Documents & Declarations

Certifications & Accuracy statements

Downloads

UL certification may be found in the UL Product iQ service by creating a free account and searching for "eGauge". PDF copies of the page are provided below. Please use the UL Product iQ service for the latest certification statement.

  • UL: United States
    Reprinted from the Online Certifications Directory with permission from UL (© 2024 UL LLC)
  • UL: Canada
    Reprinted from the Online Certifications Directory with permission from UL (© 2024 UL LLC)

AIC or short-circuit rating

  • eGauge EG4xxx and EG3xxx meters are not inline-meters and as such do not have a short-circuit current rating.  Instead, the CT sensors of the eGauge meters clamp around existing wires, so as long as those wire have suitable current rating, the installation will be safe.

Certification details by Product

eGauge Meters

Model

Safety

Accuracy

Regulatory

EG4015

IEC/UL 61010-1FTRZ

UL (CAN) FTRZ7

Overvoltage Cat III

ANSI C12.20 0.5%*

FCC Title 47 CFR Part 15- 
Subpart B Class B

CE Mark

EG4030

IEC/UL 61010-1FTRZ

UL (CAN) FTRZ7

Overvoltage Cat III

ANSI C12.20 0.5%*

FCC Title 47 CFR Part 15- 
Subpart B Class B

CE Mark

EG4215

IEC/UL 61010-1FTRZ

UL (CAN) FTRZ7

Overvoltage Cat III

ANSI C12.20 0.5%*

FCC Title 47 CFR Part 15- 
Subpart B Class B

CE Mark

EG4230

IEC/UL 61010-1(US)

UL (CAN) FTRZ7

Overvoltage Cat III

ANSI C12.20 0.5%*

FCC Title 47 CFR Part 15- 
Subpart B Class B

CE Mark

*EG4xxx meters meet ANSI C12.20 0.5% when used with approved ECS or ACT revenue grade CTs. 

 
 

AC CTs

Model Safety Accuracy Regulatory
Revenue Grade CTs      
ECS-09-R xx

UL 61010-1 XOBA

UL: 2808

UL (CAN) XOBA7

CSA 22.2

CAT III 250 Vac

ANSI C12.20 0.5%

RoHS

CE Pending

ECS20-R xxx

UL 61010-1 XOBA

UL: 2808

UL (CAN) XOBA7

CSA 22.2

CAT IV 600 VAC

ANSI C12.20 0.5%

RoHS

CE Pending

ECS36-R xxx

UL 61010-1 XOBA

UL: 2808

UL (CAN) XOBA7

CSA 22.2

CAT IV 600 VAC

ANSI C12.20 0.5%

RoHS

CE Pending

ACT-20-xxx

UL 61010-1 XOBA

UL: 2808

UL (CAN) XOBA7

CSA 22.2

CAT III 600VAC

CAT IV 250 VAC

ANSI C12.20 0.5%

IEC 60444-1 0.5s class

IEEE/ANSI C57.13, Class 0.6

CE Mark
ACT-32-xxx

UL 61010-1 XOBA

UL: 2808

UL (CAN) XOBA7

CSA 22.2

CAT III 600VAC

CAT IV 250 VAC

ANSI C12.20 0.5%

IEC 60444-1 0.5s class

IEEE/ANSI C57.13, Class 0.6

CE Mark
ACT-80-xxxx

UL 61010-1 XOBA

UL: 2808

UL (CAN) XOBA7

CSA 22.2

CAT III 600 VAC

ANSI C12.20 0.5%

IEC 60444-1 0.5s class

IEEE/ANSI C57.13, Class 0.6

CE Mark
Standard Split Core CTs      
ECS09 xx

UL 61010-1 XOBA

UL: 2808

UL (CAN) XOBA7

CSA 22.2

CAT III 250 VAC

±1% at 1% to 100% of rating

RoHS

CE Pending

ECS20 xxx

UL 61010-1 XOBA

UL: 2808

UL (CAN) XOBA7

CSA 22.2

CAT IV 600 VAC

±1% at 1% to 100% of rating

RoHS

CE Pending

ECS36 xxx

UL 61010-1 XOBA

UL: 2808

UL (CAN) XOBA7

CSA 22.2

CAT IV 600 VAC

±1% at 1% to 100% of rating

RoHS

CE Pending

J&D JSxxFL-xxx

UL Recognized

IEC61010-1

IEC/EN61869-2

CAT III 600 VAC

±1% at 1% to 100% of rating

RoHS

CE Mark

Magnelab SCT-2000

UL Recognized

CAT III 600 VAC

±1% at 10% to 130% of rating

RoHS

CE Mark

Rope CTs      
RCTxxx w/CTid

UL Recognized

UL 94 V-0

CAT III 1000 VAC

CAT IV 600 VAC

Linearity: better than 1% from (from 1 to 100% of rated current)

Positioning error: better than 4%

Minimum 30A required

CE Mark

* Revenue grade CTs meet ANSI C12.20 0.5% when used with the eGauge.

 
 

Other Sensors

 

Safety

Accuracy

Regulatory

EV1000

UL: Listed NMTR

ANSI/UL 508

UL (CAN) NMTR7

CSA C22.2

Better than 0.5%

FCC Title 47 CFR Part 15- 
Subpart B Class B

ICES-003 Information Technology Equipment Class B

PRM3

IEC/UL 61010-1 NRAQ

UL (CAN) NRAQ7

CSA C22.2

n/a

FCC Title 47 CFR Part 15- 
Subpart B Class B

ICES-003 Information Technology Equipment Class B

ESD DC CTs

UL Recognized PICQ2

CAT III 600 VAC

Linearity Error:  Better than 2%

Offset Error: Better than 1.5% of range

CE Mark