This is the same as Standard Split-Phase installation, except that the inverter feeds directly into the power utility’s grid. That is, the Solar CT is closer to the utility than the Grid CTs. This situation often arises when solar power is delivered via a line-side tap.
Example Wiring Diagram

Example Configuration

Notes
- The only difference compared to the standard installation is that
Solar+
was replaced bySolar-
in the totaling rule forUsage
. This is because the Grid CTs already capture total consumption, including any power coming from the solar system. The only exception is that when the inverter is consuming power (e.g., at night), that consumption is not captured by the Grid CTs. AddingSolar-
corrects that because it will be equal to the amount of power consumed by the inverter, or zero when the inverter is producing power.