EG41xx eGauge Pro (HomePlug, discontinued)

Discontinued Product

Model: EG41xx

 

Warning

  • The EG4130 has been discontinued and replaced with the EG4030. If HomePlug communication on a Pro meter is needed, a HomePlug adapter may be connected to the Ethernet port of the EG4030.
 

 

Overview

The eGauge Pro (EG41xx) is a high-end version of the EG4xxx meter line, featuring 15 or 30 sensor inputs and integrated HomePlug communication. For a comparison of EG4xxx models, check out the Meter Comparison Chart.

The eGauge Pro combines an energy meter, data logger, and web server, allowing you to measure, store, and retrieve data locally or remotely. It tracks power metrics (V, A, VAr, kWh, etc.) and can also integrate optional sensors for flow rate, temperature, wind speed, and more.

With a built-in user interface (UI), you can view live and historical data (up to 30 years) from a computer, tablet, or smartphone via a local network or the internet. The best part? No subscription fees—you access data directly from your eGauge hardware, not a cloud service.

 

Specifications

Measurements & Operation

  • AC Voltage: ≤ 277V L-N, ≤ 480V L-L
  • DC Voltage: +/- 60Vdc (9Vdc minimum to power)
  • Frequency: 50/60Hz
  • Power Draw: 12W max, 2W typical
  • Accuracy: ANSI C12.2 - 0.5% Compliant

Data Logger Capacity

  • Most recent hour: 1-second granularity
  • Most recent year: 1-minute granularity
  • Most recent 10-years: 15-minute granularity
  • Lifetime: 1-day granularity

Communication

  • Homeplug AV: Compatible with HomePlug AV adapter within ~100. on same phase as L1 terminal
  • Ethernet: IEEE 802.3 - LAN
  • WiFi/Cell optional with third party hardware

Safety & Regulatory

  • Safety: IEC/UL 61010-1 Ed. 3.0 B:2010
  • CE
    • IEC 61000-6-1 Ed. 3.0 B:2016
    • IEC 61000-6-3 Ed. 2.1 B:2011
  • FCC
    • FCC Title 47 CFR Part 15-Subpart B Class B
    • ICES-003 Information Technology Equipment Class B

Environmental

  • Operating Temperature: -30 to 70 deg C (-22 to 158 F)
  • Max Altitude 4000m (13,123ft)
  • Max Humidity: 80% up to 31 deg C
  • Measurement Category: Overvoltage Category III
  • Location: Open type indoor device
  • Pollution Degree: 2
 
 

Included Hardware

Optional Common Hardware (NOT Included)

 
 

Installation & Assembly