THD Registers THD is a measurement of the harmonic distortion of a signal given it's fundamental frequency, and thus may be larger than 100%. If there is insufficient amperage on a CT or the circuit is not active, the noise may calculate to high percentages. THD is typical on current waveforms depending on the load and is not always a cause for concern. The eGauge can calculate Total Harmonic Distortion (THD) on a given CT or voltage reference. Each THD measurement will use one physical register. The eGauge can measure up to the 10th harmonic. To measure THD, Navigate to Settings -> Installation Under Registers, click the "Add Registers" button Name the register as appropriate Using the dropdown menu, change the register type from P to = A second dropdown menu will appear.  Select the unit type to "total harm. dist" or "THD [%]" In the formula field, enter the following:  THD(Hz, chan("XX")) where Hz is the system frequency in Hz and XX represents either a CT (CT1, CT2, CT3, etc) or a voltage reference (L1, L2, L3). Click "Save" at the bottom of the page when finished (valid credentials required) Sample THD Register for CT1 on a 60Hz system Firmware 4.0 and later:CTx channel names have been replaced with Sx channel names. Thus, instead of using chan("CT1"), use chan("S1"). Configuration is otherwise identical:   See also eGauge Waveform View