​Monitoring 480V and 600V delta systems

The eGauge is capable of directly measuring voltages up to 277V L-N (480V L-L). In the case of a delta system with no neutral, the maximum phase-to-phase voltage is 277V as the "N" terminal of the meter has one of the line voltages connected.

A 480V or 600V delta without a neutral may be monitored by the eGauge using EV1000 High Voltage Sensors.

The below diagram shows a 480V delta system. 600V delta systems may be measured in an identical manner.

8-480V-Delta-EV1000-utility-monitor.png

 

EV1000 high voltage sensors are CTid-compatible. See this article for instructions on configuring CTid-compatible sensors.

The register configuration for the example shown above is simply S1xS4 + S2xS5. Note that your configuration may differ depending on which ports are used.

image-1636674008418.png

Proper CT/phase pairing is required for accurate readings.

 