# Identifying Rope CTs The eGauge supports Rope CTs from three different manufacturers. In order to determine which CT to select, refer to the tables below. **eGauge branded CTid rope CTs** (ERA-106-xxxx) are not meant to be manually set and should be scanned using the CTid function accessed from the eGauge Installation Settings page. For more information please see: [Configuring CTid enabled sensors](https://kb.egauge.net/books/egauge-meter-configuration/page/configuring-ctid-enabled-sensors). For **JD CTs** (colored red) there will be a label located on the CT clip itself:
CT LabelingCT Identifier on eGauge Installation Page
JRFS 115JD JRFS 115mm/4.53" 4085A
JRFS 190JD JRFS 190mm/7.48" 4085A
For **AE Accuenergy CTs** (colored orange), there is a label located on the CT lead:
CT LabelingCT Identifier on eGauge Installation Page
RCT16-1000AE RCT 106mm/4.17" 2775A
RCT24-1000AE RCT 178mm/7.01" 2775A
RCT24-2500AE RCT 178mm/7.01" 6935A
RCT36-2500AE RCT 271mm/10.67" 6935A
For the **Magnelab CTs** (colored green) there is a label located on the outside of the CT clip:
CT LabelingCT Identifier on eGauge Installation Page
RCT-1800-COILML RCT 152.4mm/6.00" 4800A
RCT-2400-COILML RCT 203.2mm/8.00" 4800A
RCT-3600-COILML RCT 279.4mm/11.00" 4800A
Note that eGauge no longer stocks Magnelab Rope CTs, but you may encounter them in the field (and the eGauge still supports them). They read very poorly below about 50A. If the CT features a separate calibration tag, this should be noted. Additional CT types are supported - see our [CT Selection Guide](https://kb.egauge.net/books/egauge-meter-configuration/page/ct-selection-guide "CT selection guide") for a more comprehensive overview. Connecting CTs which do not meet [requirements for supported CTs](https://kb.egauge.net/books/ac-and-dc-cts/page/supported-ct-types "Supported CT types") may result in reduced accuracy or damage to the eGauge.