# CT selection guide
To browse all available and supported CTs, visit the **[online store](https://store.egauge.net/sensors/current-transformers)**. For a detailed list of all CT models that have been tested to be compatible with the eGauge meter, including legacy CTs that may not be fully supported or available anymore you may view the [eGauge CT Compatibility List](https://docs.google.com/spreadsheets/d/1-LthcTQnghxqILwA9UO9d1tcgGn6htqeagIrP60EqNU/).
## Introduction A typical eGauge installation will measure the amperage of multiple conductors via multiple CT sensors. The CT sensors are installed around the current carrying conductors of the load or generation source you wish to monitor. Choosing appropriate CTs for your installation involves selecting the **mechanical dimension** and the **amperage rating** (in Amps). CTs can be used to monitor the main utility feed conductors for a facility or residence, conductors that feed sub panels, and conductors for individual circuits such as pumps, motors, air conditioning, car chargers, and lighting loads. CTs can also be used to monitor conductors from generators as well as renewable energy systems such as solar PV systems, wind generators and hydro power systems. ## CTid eGauge branded CTs are enabled with CTid technology. CTid is a technology created by eGauge which allows the eGauge meter to obtain information about a connected CT or Sensor. This information can include model, manufacturer, serial number, amperage rating (if CT), and other information about the sensor. The information is stored on a chip embedded in the CT or Sensor and can only be read by EG4xxx model units (eGauge Core and eGauge Pro). When inputs are scanned for CTid sensors, they are configured through port scanning instead of the user's traditional drop-down selection box. CTid enabled sensors also contain a locator LED that can be activated from the eGauge configuration interface. This can be used to identify which sensor is connected to which port, in the event the leads were switched or untraceable. For additional information about CTid and information on configuring please see [this article](https://kb.egauge.net/books/egauge-meter-configuration/page/configuring-ctid-enabled-sensors). ### Configuring non-CTid CTs For information on configuring sensors without CTid, see [this article](https://kb.egauge.net/books/configuration/page/what-ct-do-i-choose-from-the-ct-drop-down-selection). ## Determining how many CTs to use - 3-phase, 4-wire wye (with neutral) distribution panel feeds or individual loads require 3 CTs, one on each phase. - 3-phase, 3-wire delta (without neutral) distribution panel feeds or individual loads require 2 CTs, on each phase not connected to the eGauge’s N terminal. See the eGauge [480V or 600V delta](https://kb.egauge.net/books/egauge-installation/page/monitoring-480v-and-600v-delta-systems) and [120V or 240V delta](https://kb.egauge.net/books/egauge-installation/page/120v-or-240v-three-phase-delta) documentation for wiring diagrams. - Split-phase (phase-to-neutral) loads such as 120V residential outlets require a single CT. - Single-phase (phase-to-phase) loads such as 240V residential hot water heater require 2 CTs. If the measured load is purely single phase (no current on the neutral) such as many residential solar inverters, a single CT can be used. See configuration example 2.9 Appliances in the configuration guide for more details. - Revenue-grade accuracy monitoring requires a high-accuracy CT on each phase of the equipment to be monitored. See section 5 for more information. Some single-phase loads such as HVAC systems, dryers, and hot tubs are not balanced and will always require a CT on each phase. For example, a hot tub may have a 2-pole breaker, but use 240V for heating and 120V for lighting and pumps, which means current will be on the neutral. Facility main feeds and sub panel feeds are also not balanced. **eGauge offers these examples as a reference. The nature of the current on an appliance should be verified by a qualified electrician or via the appliance documentation before ordering.** ## Selecting the mechanical dimension of the CT CTs are available in a number of different physical sizes. The inner diameter of the CT must be large enough to fit around the conductive wire you wish to monitor. The outer dimensions must be small enough to be installed inside the circuit panel or switch gear. The tables below are provided as general sizing guidelines using eGauge CTid-enabled CTs and the alternative J&D CTs.SKU (eGauge CTid CTs) | Diameter | Wire Size |
---|---|---|
EG-ECS09-*xxx* | 9mm (0.35") | \#14 to #2 AWG |
EG-ECS20-*xxx* | 20mm (0.79") | 1/0 to 3/0 AWG |
EG-ECS36-*xxx* | 36mm (1.42") | 4/0 AWG to 400 MCM |
EG-ERA-106-*xxxx* | 106mm (4.17") | Bus bar / parallel feeds, up to 2775A |
SKU (standard CTs) | Diameter | Wire Size |
---|---|---|
JD-SCT-010-*xxx* | 10mm (0.39") | \#14 to #2 AWG |
JD-SCT-016-*xxx* | 16mm (0.63") | 1/0 to 3/0 AWG |
JD-SCT-024-*xxx* | 24mm (0.94") | 4/0 AWG to 400 MCM |
JD-SCT-036-*xxx* | 36mm (1.42") | 4/0 AWG to 400 MCM |
AE-RCT-*xxx*-*yyyy* | 106mm to 271mm (4.17" to 10.67") | Bus bar / parallel feeds, up to 6935A |